LYG-...1 Series Signal Isolators

Suitable for scenarios where signal transmission between automation instruments, control systems, and actuator structures leads to mutual interference, causing system instability and erratic data fluctuations. It is also ideal for situations where signals from different devices or instruments need to be converted to ensure compatibility. Additionally, this solution excels in cases where a single signal needs to be split into multiple channels, each routed to separate devices. ⚪ Addressing loop interference caused by multi-point grounding. ⚪ Addressing electromagnetic interference and the intrusion of higher harmonic signals. ⚪ Provides isolated power to the field transmitter and collects loop current signals for the downstream system. ⚪ Applicable on-site equipment: two-wire transmitters, three-wire transmitters, and current source signals

Key words:

Number: LYG-1100TS

Classification:

Product Description

Product Overview Product overview

The LYG-...1 series signal isolator is an intelligent instrument designed with anti-interference and signal transformation/distribution capabilities. At its core, it employs either electromagnetic or optoelectronic isolation technology to separate input and output signals, ensuring that the electrical potential reference point of the input signal (input ground) remains independent from the output signal’s reference point (output ground). This effectively suppresses common-ground loop interference commonly found in automated control systems and breaks the conductive path of interfering signals, significantly enhancing the system's overall immunity to noise. Additionally, the device can proportionally transform the input signal, delivering one or multiple user-defined electrical signals as required. It is widely used across various industrial control environments.

Performance metrics TECHNICAL PARAMETERS

Supply voltage: 18–32 VDC

Current consumption: (when powered by 24V and outputting 20mA) ≤100mA

Power Protection: Reverse Polarity Protection

On-site side input: 0–20mA, 4–20mA, 0–5V, 0–10V

Input impedance: Current input, ≤50Ω; voltage input, >200kΩ

Distribution voltage: Open circuit, ≤28V; at 20mA, ≥15.5V

Distribution current: Normal, ≤25mA; Short circuit, ≤35mA. Other input types or specification requirements will be agreed upon at the time of order.

System-side output: (0–20mA, 4–20mA, 0–5V, 0–10V)

Load resistance: Current output, 0–400Ω; voltage output >10kΩ. Other output types or specifications should be agreed upon at the time of order.

Output accuracy: 0.1% F.S.

Temperature drift: 0.01% F.S./°C

Response time: 0.1s to reach 90% of the final value

Electromagnetic Compatibility: Complies with IEC 61326-1, IEC 61326-3-1

Operating environment temperature: -20°C to +60°C

Insulation strength: Field side – system side, ≥1500 VAC; Power supply – system side, ≥500 VAC

Insulation resistance: Field side – System side, ≥100 MΩ; Power supply – System side, ≥100 MΩ

Product weight: approximately 150g